CJPS C-450 WP1
Engine: Cummins 6ZTAA13-G4
- Prime
- 450 kVA
- Standby
- 495 kVA
- Alternator
- Stamford S4L1D-G41
- Cooling
- Water Cooled
- Fuel @ 75%
- 66.8 L/hr
Open TypeOption: Silent




Open Frame
*Photo is a product illustration; actual specifications may differ.
JERBINDO CJPS C-450 WP3 is a diesel generator rated at 450 kVA prime and 495 kVA standby, powered by a water-cooled Cummins KTA19-G3 engine with a Stamford alternator. The unit is designed for power needs in hospital, hotel, office tower, with high operational reliability and optimal fuel efficiency.
| Cooling System | Water Cooled |
|---|---|
| Engine Brand | Cummins |
| Engine Model | KTA19-G3 |
| Aspiration | Turbocharged, Charge Air Cooled |
|---|---|
| Cylinder Arrangement | 6 in-line |
| Cylinders | 6 |
| Displacement | 19 L |
| Bore | 159 mm |
| Stroke | 159 mm |
| Governor | Electronic |
| Max Engine Power | 448 kWm |
| Oil Capacity | 50 L |
| Brand & Model | Stamford S4L1D-G41 |
|---|---|
| Power Factor | Voltage | 0.8 | 380 V |
| Prime Output | 450 kVA | 360 kW |
|---|---|
| Standby Output | 495 kVA | 396 kW |
| Voltage | Frequency | Speed | 380 V | 50 Hz | 1500 rpm |
| Open Type (standard) | Silent Canopy (optional) | |
|---|---|---|
| Dimensions (L×W×H) | 3485 x 1155 x 1640 mm | 4400 x 1800 x 2600 mm |
| Dry Weight | 3870 kg | 4870 kg |
Units ship as open type as standard. Silent canopy dimensions are indicative and may change with the canopy specification (noise level, fuel tank capacity, service access).
This unit is designed for hospital, hotel, office tower. With water-cooled operation and a prime rating of 450 kVA, it supports continuous and backup operation in facilities that need high reliability.
The 450 kVA prime rating applies when the generator is the main power source under varying loads, for example at sites without a stable grid supply. The 495 kVA standby rating is for backup during outages, with use limited to no more than 10% of total annual operating hours.
Yes. JERBINDO units come as an open frame for enclosed engine rooms and with a silent canopy for areas that need lower noise. Dimensions and weight differ by configuration; state your preference when requesting a quotation.
Prepare your estimated total load in kW or kVA, the operating type (prime or standby), the installation location, your enclosure preference (open or silent), any ATS or AMF panel needs, and your target operating date. This helps our team recommend the right unit and price.



Engine: Cummins 6ZTAA13-G4
Open TypeOption: Silent



Engine: Cummins QSZ13-G5
Open TypeOption: Silent



Engine: Cummins QSX15-G6
Open TypeOption: Silent



Engine: Deutz BF 8M 1015 C
Open TypeOption: Silent

Discuss your power requirements with our sales and service team to get the right products and services.