CJPS C-625 WP
Engine: Cummins KTAA19-G6A
- Prime
- 625 kVA
- Standby
- 687.5 kVA
- Alternator
- Stamford S5L1D-F4
- Cooling
- Water Cooled
- Fuel @ 75%
- 95.2 L/hr
Open TypeOption: Silent




Open Frame
*Photo is a product illustration; actual specifications may differ.
JERBINDO CJPS O-636 WP is a diesel generator rated at 636 kVA prime and 699.6 kVA standby, powered by a water-cooled Cummins VTA28-G5 engine with a Stamford alternator. The unit is designed for power needs in data center, hospital, commercial complex, with high operational reliability and optimal fuel efficiency.
| Cooling System | Water Cooled |
|---|---|
| Engine Brand | Cummins |
| Engine Model | VTA28-G5 |
| Aspiration | Turbocharged, Charge Air Cooled |
|---|---|
| Cylinder Arrangement | 12 in-line |
| Cylinders | 12 |
| Displacement | 28 L |
| Bore | 139.7 mm |
| Stroke | 152.4 mm |
| Governor | Electronic |
| Max Engine Power | 612 kWm |
| Oil Capacity | 38 L |
| Brand & Model | Stamford S5L1D-F4 |
|---|---|
| Power Factor | Voltage | 0.8 | 380 V |
| Prime Output | 636 kVA | 509 kW |
|---|---|
| Standby Output | 699.6 kVA | 559.9 kW |
| Voltage | Frequency | Speed | 380 V | 50 Hz | 1500 rpm |
| Open Type (standard) | Silent Canopy (optional) | |
|---|---|---|
| Dimensions (L×W×H) | 3600 x 1700 x 2300 mm | 4900 x 1800 x 2700 mm |
| Dry Weight | 4950 kg | 5700 kg |
Units ship as open type as standard. Silent canopy dimensions are indicative and may change with the canopy specification (noise level, fuel tank capacity, service access).
This unit is designed for data center, hospital, commercial complex. With water-cooled operation and a prime rating of 636 kVA, it supports continuous and backup operation in facilities that need high reliability.
The 636 kVA prime rating applies when the generator is the main power source under varying loads, for example at sites without a stable grid supply. The 699.6 kVA standby rating is for backup during outages, with use limited to no more than 10% of total annual operating hours.
Yes. JERBINDO units come as an open frame for enclosed engine rooms and with a silent canopy for areas that need lower noise. Dimensions and weight differ by configuration; state your preference when requesting a quotation.
Prepare your estimated total load in kW or kVA, the operating type (prime or standby), the installation location, your enclosure preference (open or silent), any ATS or AMF panel needs, and your target operating date. This helps our team recommend the right unit and price.



Engine: Cummins KTAA19-G6A
Open TypeOption: Silent



Engine: Cummins VTA28-G5
Open TypeOption: Silent



Engine: Cummins QSK19-G4
Open TypeOption: Silent



Engine: Cummins KTA19G9A
Open TypeOption: Silent

Discuss your power requirements with our sales and service team to get the right products and services.