500 kVA Generator

Equal to 400 kW. Cummins, Deutz, Perkins & Baudouin engines, open and silent, with fuel use and dimensions compared.

View Catalogue
Overview

Getting to Know 500 kVA Generators

A 500 kVA generator is about 400 kW at a power factor of 0.8. This class is widely used as main or backup power for buildings, hotels, hospitals and mid-size factories.

Buyers rarely say prime or standby. If you need 500 kVA as main power, choose a 500 kVA prime model. If it is only backup during grid outages, a 450–455 kVA prime model with a standby rating of about 500 kVA is usually enough.

Suited to

  • Office buildings
  • Hotels
  • Hospitals
  • Apartments
  • Campuses & schools
  • Small and mid-size factories

Prime or Standby?

Main power

500 kVA prime

10models
  • The generator is the main power source, for example at a site without grid power
  • It runs long hours every day with a varying load

e.g. BJPS-500-WP

Grid backup

500 kVA standby

7models
  • The generator only runs during grid outages
  • Prime slightly below 500 kVA, standby around 500 kVA: usually more economical

e.g. CJPS C-450 WP1

Model

500 kVA Generator Options

Every JERBINDO 500 kVA model by engine brand. Select a model for full specifications.

Cummins engine

Fuel at 75% (prime): 74–82 L/hr10 models
ModelPrime kVAStandby kVA
CJPS C-500 WPQSZ13-G10500 kVA prime500550
CJPS C-500 WP1 (CCEC)QSZ13-G3500 kVA prime500550
CJPS C-500 WP1 (DCEC)QSZ13-G3500 kVA prime500550
CJPS C-500 WP2KTA19-G3A500 kVA prime500550
CJPS C-500 WP3KTA19-G4500 kVA prime500550
CJPS O-500 WPQSX15-G8500 kVA prime500550
CJPS C-450 WP16ZTAA13-G4500 kVA standby450495
CJPS C-450 WP2QSZ13-G5500 kVA standby450495
CJPS C-450 WP3KTA19-G3500 kVA standby450495
CJPS O-450 WPQSX15-G6500 kVA standby450495
Cummins Generator

Deutz engine

Fuel at 75% (prime): 84.9 L/hr3 models
ModelPrime kVAStandby kVA
DJPS-500 WPBF8M 1015 CP500 kVA prime500550
DJPS-500 WP-LBF8M 1015 CP500 kVA prime500550
DJPS-450 WPBF 8M 1015 C500 kVA standby450495
Deutz Generator

Perkins engine

Fuel at 75% (prime): 81 L/hr3 models
ModelPrime kVAStandby kVA
PJPS-500 WP2506 C-E15TAG2500 kVA prime500550
PJPS-450 WP2506 C-E15TAG1500 kVA standby450495
PJPS-455 WP2506 C-E15TAG1500 kVA standby455500.5
Perkins Generator

Baudouin engine

1 models
ModelPrime kVAStandby kVA
BJPS-500-WP6M21G550/5500 kVA prime500550
Baudouin Generator
Installation

Generator Room Requirements

General guidance for the 500 kVA class from engine and generator makers' installation manuals. Final figures follow the installation drawings and datasheet of the chosen unit.

Minimum room, 1 unit
6.6 × 4.5 m
Open type (L × W × H)
3000–3600 × 1155–1500 × 1640–2100 mm
Silent canopy (L × W × H)
4400 × 1800 × 2400–2600 mm

Service clearance

1.5 m per side

  • Leave at least about 1.5 m of clear space on every side of the generator for maintenance (Cummins' guide for units from 100 kVA; other sources give 0.9–1.2 m), plus room above it to open panels. With the largest open unit in this class, one generator needs a room of at least about 6.6 × 4.5 m.
  • When installing more than one unit, leave about 2 m between generators.

Ventilation

Outlet ≈ 1.5× radiator

  • Provide an air inlet behind the generator and an outlet in front of the radiator. As a general guide, the outlet is about 1.5× the radiator core area and the inlet 1.5–2× (louvres cut the free area by about 25%). Keep the room no more than about 7–10 °C above outdoor air; above 40 °C the generator needs derating.
  • Fit a duct adaptor from the radiator to the outlet so hot air does not circulate back into the room.

Foundation

≥ 2× unit weight

  • A concrete foundation of at least about 2× the generator's weight, extending 150–300 mm beyond the skid on every side, with vibration isolators between the skid and the foundation. Let the concrete cure for 28 days before loading. Dry weight of the open units in this class: 3.7–4.9 tonnes.

Day tank

590–680 L / 8 hours

  • Fuel use at 75% load: 74–84.9 L/hr, or about 590–680 L for 8 hours of running. Size the day tank from this; for longer running add a bulk tank with a transfer pump.
  • NFPA 37 limits a tank inside the generator room to 2,500 L unless it has its own fire-rated room; local regulations also apply.

Exhaust

Backpressure ≤ datasheet

  • A flexible connector at the engine outlet; pipework supported on its own so it does not load the engine, insulated and fitted with a rain cap. Choose the pipe and silencer so backpressure stays within the engine datasheet limit; avoid long runs and many bends. Discharge away from the air inlet.

Configuration

Open · Silent · Mobile

  • Open units for an enclosed generator room; silent canopy units for outdoors.
  • An ATS/AMF panel for grid backup; a synchronizing panel for two or more units running in parallel.
  • Silent mobile is available for needs that move between sites.
FAQ

Frequently Asked Questions

How much does a 500 kVA generator cost?

The price of a 500 kVA generator depends on the engine brand, the configuration (open type, silent canopy, silent mobile), an ATS/AMF or synchronizing panel, installation and commissioning, the delivery location, and the warranty and after-sales service. Use Request a Quote with your requirements and our sales team will send a quotation.

How many kW is a 500 kVA generator?

At the 0.8 power factor commonly used for generators, 500 kVA equals 400 kW. The exact kW of each model is on its specification page.

How much diesel does a 500 kVA generator use?

At 75% load, the 500 kVA prime generators in our catalogue use about 74–84.9 L/hr, depending on the engine brand and model. Fuel use at 50% and 100% load is on each model's page.

Should I choose 500 kVA prime or standby?

Choose a 500 kVA prime model if the generator is the main power source or runs long hours with a varying load. If you need 500 kVA only as backup during grid outages, a model with a 500 kVA standby rating (and a slightly lower prime rating) is usually enough and more economical.

By the Numbers

Trusted by Various Companies

Decades of experience and a portfolio of projects across many sectors reflect our commitment to quality.

Our clients

  • Otsuka
  • BCA
  • Santos Jaya Abadi
  • Bank Indonesia
  • Telkom Indonesia
  • Adhi Karya
  • IKEA
  • JW Marriott
  • Spazio
  • Universitas Brawijaya
  • PUPR
  • Siloam Hospitals
  • Djarum
  • Avian Brands
  • PLN
  • Waskita
  • KAI
  • Ciputra World
  • Hero
  • Golden Palace Hotel
  • Institut Teknologi Bandung
  • Universitas Negeri Surabaya
  • Pemerintah Kota Mataram
  • Kievit
  • Gudang Garam
  • Polygon
  • Pertamina Geothermal Energy
  • WIKA
  • INKA
  • Giant
  • Ibis Hotel
  • Universitas Gadjah Mada
  • Universitas Ciputra
  • Pemerintah Kota Surabaya
  • Huawei
  • MNC
  • Kapal Api
  • PGN
  • PP Properti
  • Bulog
  • Transmart
  • Vasa Hotel
  • Westown View
  • Universitas Airlangga
  • Kementerian Sosial
  • National Hospital
Need a generator for your business?

Find the Right Industrial Generator Solution

Discuss your power requirements with our sales and service team to get the right products and services.

1977
Experienced since
ISO
9001 · 14001 · 45001
TKDN
Certified products
2
Offices & workshops

Tell Us What You Need

Provide the following information so our team can respond with a solution suited to your requirements.