20 kVA Generator
Equal to 16 kW. Deutz, Baudouin, Cummins & Perkins engines, open and silent, with fuel use and dimensions compared.

Getting to Know 20 kVA Generators
A 20 kVA generator is about 16 kW at a power factor of 0.8. This small class serves as backup power for shophouses, small offices, clinics and telecom equipment.
Besides the JERBINDO models below, VOLTRAGEN also offers a 20 kVA unit, built with a silent canopy as standard for sites close to homes.
Suited to
- Shophouses & stores
- Small offices
- Clinics
- Telecommunications
- Homes
Prime or Standby?
Main power
20 kVA prime
- The generator is the main power source, for example at a site without grid power
- It runs long hours every day with a varying load
e.g. CJPS C-20 WP
Grid backup
20 kVA standby
- The generator only runs during grid outages
- Prime slightly below 20 kVA, standby around 20 kVA: usually more economical
e.g. BJPS-18-WP
20 kVA Generator Options
Every JERBINDO 20 kVA model by engine brand. Select a model for full specifications.
Deutz engine
Fuel at 75% (prime): 4.2 L/hr2 models
| Model | Prime kVA | Standby kVA |
|---|---|---|
| DJPS-20 OP1201120 kVA prime | 20 | 22 |
| DJPS-20 OP2F3M 201120 kVA prime | 20 | 22 |
Baudouin engine
1 models
| Model | Prime kVA | Standby kVA |
|---|---|---|
| BJPS-18-WP6M21G500/520 kVA standby | 18 | 20 |
Cummins engine
Fuel at 75% (prime): 5.2 L/hr1 models
| Model | Prime kVA | Standby kVA |
|---|---|---|
| CJPS C-20 WP4B3.9-G1120 kVA prime | 20 | 22 |
Perkins engine
Fuel at 75% (prime): 4 L/hr1 models
| Model | Prime kVA | Standby kVA |
|---|---|---|
| PJPS-20 WP404A-22G120 kVA prime | 20 | 22 |
Generator Room Requirements
General guidance for the 20 kVA class from engine and generator makers' installation manuals. Final figures follow the installation drawings and datasheet of the chosen unit.
- Minimum room, 1 unit
- 4.8 × 4.0 m
- Open type (L × W × H)
- 1300–1750 × 700–1000 × 1070–1530 mm
- Silent canopy (L × W × H)
- 2000–2100 × 1000 × 1400–1470 mm
Service clearance
1.5 m per side
- Leave at least about 1.5 m of clear space on every side of the generator for maintenance (Cummins' guide for units from 100 kVA; other sources give 0.9–1.2 m), plus room above it to open panels. With the largest open unit in this class, one generator needs a room of at least about 4.8 × 4.0 m.
Ventilation
Outlet ≈ 1.5× radiator
- Provide an air inlet behind the generator and an outlet in front of the radiator. As a general guide, the outlet is about 1.5× the radiator core area and the inlet 1.5–2× (louvres cut the free area by about 25%). Keep the room no more than about 7–10 °C above outdoor air; above 40 °C the generator needs derating.
- In this class the radiator fan is usually enough, as long as the openings are not blocked.
Foundation
≥ 2× unit weight
- A concrete foundation of at least about 2× the generator's weight, extending 150–300 mm beyond the skid on every side, with vibration isolators between the skid and the foundation. Let the concrete cure for 28 days before loading. Dry weight of the open units in this class: 0.5–1 tonnes.
Day tank
30–40 L / 8 hours
- Fuel use at 75% load: 4–5.2 L/hr, or about 30–40 L for 8 hours of running. Size the day tank from this; for longer running add a bulk tank with a transfer pump.
- NFPA 37 limits a tank inside the generator room to 2,500 L unless it has its own fire-rated room; local regulations also apply.
Exhaust
Backpressure ≤ datasheet
- A flexible connector at the engine outlet; pipework supported on its own so it does not load the engine, insulated and fitted with a rain cap. Choose the pipe and silencer so backpressure stays within the engine datasheet limit; avoid long runs and many bends. Discharge away from the air inlet.
Configuration
Open · Silent · Mobile
- Silent canopy units suit open areas or sites near homes; open units suit an enclosed generator room.
- As grid backup, the generator is installed with an ATS/AMF panel so it starts automatically during an outage.
Generator Projects Around 20 kVA
Projects from our project list with units of around 20 kVA.
More project references, 2021–2026
6 projects with units of around 20 kVA in our 2021–2026 project list. Client names are not shown.
FAW 5 × 20 kVA
Place of worship
Merauke, South Papua · 2025
FAW 20 kVA
Hotel & resort
Malang, East Java · 2024
FAW 20 kVA
Bank office
Jember, East Java · 2023
FAW 20 kVA
Government office
Ambon, Maluku · 2023
Perkins 20 kVA
Office building
Sorong, Southwest Papua · 2021
Perkins 20 kVA
Office building
Malang, East Java · 2021
Frequently Asked Questions
How much does a 20 kVA generator cost?
The price of a 20 kVA generator depends on the engine brand, the configuration (open type, silent canopy, silent mobile), an ATS/AMF or synchronizing panel, installation and commissioning, the delivery location, and the warranty and after-sales service. Use Request a Quote with your requirements and our sales team will send a quotation. What shapes a generator price
How many kW is a 20 kVA generator?
At the 0.8 power factor commonly used for generators, 20 kVA equals 16 kW. The exact kW of each model is on its specification page.
How much diesel does a 20 kVA generator use?
At 75% load, the 20 kVA prime generators in our catalogue use about 4–5.2 L/hr, depending on the engine brand and model. Fuel use at 50% and 100% load is on each model's page.
Should I choose 20 kVA prime or standby?
Choose a 20 kVA prime model if the generator is the main power source or runs long hours with a varying load. If you need 20 kVA only as backup during grid outages, a model with a 20 kVA standby rating (and a slightly lower prime rating) is usually enough and more economical.