50 kVA Generator
Equal to 40 kW. Deutz, Baudouin, Cummins & Perkins engines, open and silent, with fuel use and dimensions compared.

Getting to Know 50 kVA Generators
A 50 kVA generator is about 40 kW at a power factor of 0.8. This class is popular with offices, schools, clinics and shops that want their whole load to stay on during an outage.
Besides the JERBINDO models below, VOLTRAGEN also offers a 50 kVA unit with a silent canopy as standard.
Suited to
- Offices
- Schools
- Clinics
- Restaurants
- Retail & minimarkets
- Small warehouses
Prime or Standby?
Main power
50 kVA prime
- The generator is the main power source, for example at a site without grid power
- It runs long hours every day with a varying load
e.g. BJPS-50-WP
Grid backup
50 kVA standby
- The generator only runs during grid outages
- Prime slightly below 50 kVA, standby around 50 kVA: usually more economical
e.g. DJPS-45 AP
50 kVA Generator Options
Every JERBINDO 50 kVA model by engine brand. Select a model for full specifications.
Deutz engine
Fuel at 75% (prime): 11 L/hr2 models
| Model | Prime kVA | Standby kVA |
|---|---|---|
| DJPS-50 APF6L91250 kVA prime | 50 | 55 |
| DJPS-45 APF4L91450 kVA standby | 45 | 49.5 |
Baudouin engine
Fuel at 75% (prime): 8.9 L/hr1 models
| Model | Prime kVA | Standby kVA |
|---|---|---|
| BJPS-50-WP4M06G55/550 kVA prime | 50 | 55 |
Cummins engine
Fuel at 75% (prime): 7.8 L/hr1 models
| Model | Prime kVA | Standby kVA |
|---|---|---|
| CJPS C-50 WP4BTA3.9-G250 kVA prime | 50 | 55 |
Perkins engine
1 models
| Model | Prime kVA | Standby kVA |
|---|---|---|
| PJPS-45 WP11103A-33TG150 kVA standby | 45 | 49.5 |
Generator Room Requirements
General guidance for the 50 kVA class from engine and generator makers' installation manuals. Final figures follow the installation drawings and datasheet of the chosen unit.
- Minimum room, 1 unit
- 5.0 × 4.0 m
- Open type (L × W × H)
- 1775–2000 × 685–970 × 805–1530 mm
- Silent canopy (L × W × H)
- 2600 × 1200 × 1500–1530 mm
Service clearance
1.5 m per side
- Leave at least about 1.5 m of clear space on every side of the generator for maintenance (Cummins' guide for units from 100 kVA; other sources give 0.9–1.2 m), plus room above it to open panels. With the largest open unit in this class, one generator needs a room of at least about 5.0 × 4.0 m.
Ventilation
Outlet ≈ 1.5× radiator
- Provide an air inlet behind the generator and an outlet in front of the radiator. As a general guide, the outlet is about 1.5× the radiator core area and the inlet 1.5–2× (louvres cut the free area by about 25%). Keep the room no more than about 7–10 °C above outdoor air; above 40 °C the generator needs derating.
- In this class the radiator fan is usually enough, as long as the openings are not blocked.
Foundation
≥ 2× unit weight
- A concrete foundation of at least about 2× the generator's weight, extending 150–300 mm beyond the skid on every side, with vibration isolators between the skid and the foundation. Let the concrete cure for 28 days before loading. Dry weight of the open units in this class: 0.6–1.1 tonnes.
Day tank
60–90 L / 8 hours
- Fuel use at 75% load: 7.8–11 L/hr, or about 60–90 L for 8 hours of running. Size the day tank from this; for longer running add a bulk tank with a transfer pump.
- NFPA 37 limits a tank inside the generator room to 2,500 L unless it has its own fire-rated room; local regulations also apply.
Exhaust
Backpressure ≤ datasheet
- A flexible connector at the engine outlet; pipework supported on its own so it does not load the engine, insulated and fitted with a rain cap. Choose the pipe and silencer so backpressure stays within the engine datasheet limit; avoid long runs and many bends. Discharge away from the air inlet.
Configuration
Open · Silent · Mobile
- Silent canopy units for open areas or sites near homes; open units for an enclosed generator room.
- As grid backup, the generator is installed with an ATS/AMF panel so it starts automatically during an outage.
Generator Projects Around 50 kVA
Projects from our project list with units of around 50 kVA.
6 projects with units of around 50 kVA in our 2021–2026 project list. Client names are not shown.
Baudouin 50 kVA
Clinic & laboratory
Surabaya, East Java · 2026
Deutz 50 kVA
Substation & power grid
East Kalimantan · 2025
Cummins 50 kVA
Government office
North Sulawesi · 2024
Baudouin 50 kVA
School
Bogor, West Java · 2024
FAW 50 kVA
Office building
Lampung · 2022
Baudouin 50 kVA
Clinic & laboratory
Klungkung, Bali · 2025
Frequently Asked Questions
How much does a 50 kVA generator cost?
The price of a 50 kVA generator depends on the engine brand, the configuration (open type, silent canopy, silent mobile), an ATS/AMF or synchronizing panel, installation and commissioning, the delivery location, and the warranty and after-sales service. Use Request a Quote with your requirements and our sales team will send a quotation. What shapes a generator price
How many kW is a 50 kVA generator?
At the 0.8 power factor commonly used for generators, 50 kVA equals 40 kW. The exact kW of each model is on its specification page.
How much diesel does a 50 kVA generator use?
At 75% load, the 50 kVA prime generators in our catalogue use about 7.8–11 L/hr, depending on the engine brand and model. Fuel use at 50% and 100% load is on each model's page.
Should I choose 50 kVA prime or standby?
Choose a 50 kVA prime model if the generator is the main power source or runs long hours with a varying load. If you need 50 kVA only as backup during grid outages, a model with a 50 kVA standby rating (and a slightly lower prime rating) is usually enough and more economical.