400 kVA Generator
Equal to 320 kW. Cummins, Baudouin, Deutz & Perkins engines, open and silent, with fuel use and dimensions compared.
Getting to Know 400 kVA Generators
A 400 kVA generator is about 320 kW at a power factor of 0.8. This class serves hotels, hospitals, multi-storey buildings and mid-size factories.
The 400 kVA class offers several engine options, with fuel use and dimensions compared directly in the table.
Suited to
- Hotels
- Hospitals
- Multi-storey buildings
- Mid-size factories
- Malls
- Campuses
Prime or Standby?
Main power
400 kVA prime
- The generator is the main power source, for example at a site without grid power
- It runs long hours every day with a varying load
e.g. CJPS C-400 WP1
Grid backup
400 kVA standby
- The generator only runs during grid outages
- Prime slightly below 400 kVA, standby around 400 kVA: usually more economical
e.g. BJPS-375-WP
400 kVA Generator Options
Every JERBINDO 400 kVA model by engine brand. Select a model for full specifications.
Cummins engine
Fuel at 75% (prime): 60–73.3 L/hr3 models
| Model | Prime kVA | Standby kVA |
|---|---|---|
| CJPS C-400 WP1QSZ13-G7400 kVA prime | 400 | 440 |
| CJPS C-400 WP2NTAA855-G7A400 kVA prime | 400 | 440 |
| CJPS C-400WPQSG12-G4400 kVA prime | 400 | 440 |
Baudouin engine
1 models
| Model | Prime kVA | Standby kVA |
|---|---|---|
| BJPS-375-WP6M21G400/5400 kVA standby | 375 | 400 |
Deutz engine
Fuel at 75% (prime): 69.3 L/hr1 models
| Model | Prime kVA | Standby kVA |
|---|---|---|
| DJPS-400 WPBF8M 1015 C400 kVA prime | 400 | 440 |
Perkins engine
Fuel at 75% (prime): 65 L/hr1 models
| Model | Prime kVA | Standby kVA |
|---|---|---|
| PJPS-400 WP2206 C-E13TAG3400 kVA prime | 400 | 440 |
Generator Room Requirements
General guidance for the 400 kVA class from engine and generator makers' installation manuals. Final figures follow the installation drawings and datasheet of the chosen unit.
- Minimum room, 1 unit
- 6.5 × 4.5 m
- Open type (L × W × H)
- 2900–3500 × 1300–1500 × 1800–2100 mm
- Silent canopy (L × W × H)
- 4200–4400 × 1600–1800 × 2600–2615 mm
Service clearance
1.5 m per side
- Leave at least about 1.5 m of clear space on every side of the generator for maintenance (Cummins' guide for units from 100 kVA; other sources give 0.9–1.2 m), plus room above it to open panels. With the largest open unit in this class, one generator needs a room of at least about 6.5 × 4.5 m.
- When installing more than one unit, leave about 2 m between generators.
Ventilation
Outlet ≈ 1.5× radiator
- Provide an air inlet behind the generator and an outlet in front of the radiator. As a general guide, the outlet is about 1.5× the radiator core area and the inlet 1.5–2× (louvres cut the free area by about 25%). Keep the room no more than about 7–10 °C above outdoor air; above 40 °C the generator needs derating.
- Fit a duct adaptor from the radiator to the outlet so hot air does not circulate back into the room.
Foundation
≥ 2× unit weight
- A concrete foundation of at least about 2× the generator's weight, extending 150–300 mm beyond the skid on every side, with vibration isolators between the skid and the foundation. Let the concrete cure for 28 days before loading. Dry weight of the open units in this class: 3–4.9 tonnes.
Day tank
480–590 L / 8 hours
- Fuel use at 75% load: 60–73.3 L/hr, or about 480–590 L for 8 hours of running. Size the day tank from this; for longer running add a bulk tank with a transfer pump.
- NFPA 37 limits a tank inside the generator room to 2,500 L unless it has its own fire-rated room; local regulations also apply.
Exhaust
Backpressure ≤ datasheet
- A flexible connector at the engine outlet; pipework supported on its own so it does not load the engine, insulated and fitted with a rain cap. Choose the pipe and silencer so backpressure stays within the engine datasheet limit; avoid long runs and many bends. Discharge away from the air inlet.
Configuration
Open · Silent · Mobile
- Open units for a generator room; silent canopy units for outdoors.
- An ATS/AMF panel for grid backup; a synchronizing panel for parallel operation of several units.
Generator Projects Around 400 kVA
Projects from our project list with units of around 400 kVA.
More project references, 2021–2026
9 projects with units of around 400 kVA in our 2021–2026 project list. Client names are not shown.
Baudouin 400 kVA
Residential tower
Nusantara Capital City (IKN) · 2025
Baudouin 400 kVA
Substation & power grid
West Java · 2025
Baudouin 400 kVA
Hospital
Manggarai Timur, East Nusa Tenggara · 2025
Cummins 400 kVA
Government office
Bandung, West Java · 2023
Perkins 400 kVA
University
Malang, East Java · 2022
Cummins 400 kVA
Warehouse & cold storage
Surabaya, East Java · 2021
Cummins 400 kVA
Residential tower
Nusantara Capital City (IKN) · 2024
Baudouin 400 kVA
Substation & power grid
Probolinggo, East Java · 2024
Frequently Asked Questions
How much does a 400 kVA generator cost?
The price of a 400 kVA generator depends on the engine brand, the configuration (open type, silent canopy, silent mobile), an ATS/AMF or synchronizing panel, installation and commissioning, the delivery location, and the warranty and after-sales service. Use Request a Quote with your requirements and our sales team will send a quotation. What shapes a generator price
How many kW is a 400 kVA generator?
At the 0.8 power factor commonly used for generators, 400 kVA equals 320 kW. The exact kW of each model is on its specification page.
How much diesel does a 400 kVA generator use?
At 75% load, the 400 kVA prime generators in our catalogue use about 60–73.3 L/hr, depending on the engine brand and model. Fuel use at 50% and 100% load is on each model's page.
Should I choose 400 kVA prime or standby?
Choose a 400 kVA prime model if the generator is the main power source or runs long hours with a varying load. If you need 400 kVA only as backup during grid outages, a model with a 400 kVA standby rating (and a slightly lower prime rating) is usually enough and more economical.