30 kVA Generator
Equal to 24 kW. Deutz, Cummins & Perkins engines, open and silent, with fuel use and dimensions compared.

Getting to Know 30 kVA Generators
A 30 kVA generator is about 24 kW at a power factor of 0.8. It is enough to back up a small business such as a restaurant, a minimarket or an office with several air conditioners.
Besides the JERBINDO models below, VOLTRAGEN also offers a 30 kVA unit with a silent canopy as standard for noise-restricted sites.
Suited to
- Restaurants & cafés
- Minimarkets
- Small offices
- Clinics
- Schools
- Telecommunications
Prime or Standby?
Main power
30 kVA prime
- The generator is the main power source, for example at a site without grid power
- It runs long hours every day with a varying load
e.g. CJPS C-30 WP
Grid backup
30 kVA standby
- The generator only runs during grid outages
- The 30 kVA prime models already have a standby rating of about 33 kVA
Use the 30 kVA prime models
30 kVA Generator Options
Every JERBINDO 30 kVA model by engine brand. Select a model for full specifications.
Deutz engine
Fuel at 75% (prime): 5.7–7.4 L/hr3 models
| Model | Prime kVA | Standby kVA |
|---|---|---|
| DJPS-30 OPF4L201130 kVA prime | 30 | 33 |
| DJPS-30 OP1BF4L201130 kVA prime | 30 | 33 |
| DJPS-30 OP2F4M201130 kVA prime | 30 | 33 |
Cummins engine
Fuel at 75% (prime): 5.4 L/hr2 models
| Model | Prime kVA | Standby kVA |
|---|---|---|
| CJPS C-30 WP4BT3.9-G130 kVA prime | 30 | 33 |
| CJPS C-30 WP24BT3.9-G1230 kVA prime | 30 | 33 |
Perkins engine
Fuel at 75% (prime): 5.4 L/hr1 models
| Model | Prime kVA | Standby kVA |
|---|---|---|
| PJPS-30 WP11103A-33G30 kVA prime | 30 | 33 |
Generator Room Requirements
General guidance for the 30 kVA class from engine and generator makers' installation manuals. Final figures follow the installation drawings and datasheet of the chosen unit.
- Minimum room, 1 unit
- 4.8 × 4.0 m
- Open type (L × W × H)
- 1280–1750 × 760–970 × 1200–1530 mm
- Silent canopy (L × W × H)
- 2200–2250 × 1000–1100 × 1400–1500 mm
Service clearance
1.5 m per side
- Leave at least about 1.5 m of clear space on every side of the generator for maintenance (Cummins' guide for units from 100 kVA; other sources give 0.9–1.2 m), plus room above it to open panels. With the largest open unit in this class, one generator needs a room of at least about 4.8 × 4.0 m.
Ventilation
Outlet ≈ 1.5× radiator
- Provide an air inlet behind the generator and an outlet in front of the radiator. As a general guide, the outlet is about 1.5× the radiator core area and the inlet 1.5–2× (louvres cut the free area by about 25%). Keep the room no more than about 7–10 °C above outdoor air; above 40 °C the generator needs derating.
- In this class the radiator fan is usually enough, as long as the openings are not blocked.
Foundation
≥ 2× unit weight
- A concrete foundation of at least about 2× the generator's weight, extending 150–300 mm beyond the skid on every side, with vibration isolators between the skid and the foundation. Let the concrete cure for 28 days before loading. Dry weight of the open units in this class: 0.8–1 tonnes.
Day tank
40–60 L / 8 hours
- Fuel use at 75% load: 5.4–7.4 L/hr, or about 40–60 L for 8 hours of running. Size the day tank from this; for longer running add a bulk tank with a transfer pump.
- NFPA 37 limits a tank inside the generator room to 2,500 L unless it has its own fire-rated room; local regulations also apply.
Exhaust
Backpressure ≤ datasheet
- A flexible connector at the engine outlet; pipework supported on its own so it does not load the engine, insulated and fitted with a rain cap. Choose the pipe and silencer so backpressure stays within the engine datasheet limit; avoid long runs and many bends. Discharge away from the air inlet.
Configuration
Open · Silent · Mobile
- Silent canopy units for open areas or sites near homes; open units for an enclosed generator room.
- An ATS/AMF panel starts the generator and transfers the load automatically during a grid outage.
Generator Projects Around 30 kVA
Projects from our project list with units of around 30 kVA.
8 projects with units of around 30 kVA in our 2021–2026 project list. Client names are not shown.
Baudouin 30 kVA
Office building
Jakarta · 2026
Cummins 30 kVA
Bank office
Tuban, East Java · 2026
Baudouin 30 kVA
Aquaculture
Sumbawa, West Nusa Tenggara · 2025
Cummins 30 kVA
Substation & power grid
Manado, North Sulawesi · 2023
FAW 30 kVA
Retail & commercial
Malang, East Java · 2023
Cummins 30 kVA
Office building
Kupang, East Nusa Tenggara · 2025
FAW 30 kVA
Retail & commercial
Yogyakarta · 2021
Deutz 30 kVA
Office building
Surabaya, East Java · 2024
Frequently Asked Questions
How much does a 30 kVA generator cost?
The price of a 30 kVA generator depends on the engine brand, the configuration (open type, silent canopy, silent mobile), an ATS/AMF or synchronizing panel, installation and commissioning, the delivery location, and the warranty and after-sales service. Use Request a Quote with your requirements and our sales team will send a quotation. What shapes a generator price
How many kW is a 30 kVA generator?
At the 0.8 power factor commonly used for generators, 30 kVA equals 24 kW. The exact kW of each model is on its specification page.
How much diesel does a 30 kVA generator use?
At 75% load, the 30 kVA prime generators in our catalogue use about 5.4–7.4 L/hr, depending on the engine brand and model. Fuel use at 50% and 100% load is on each model's page.
Should I choose 30 kVA prime or standby?
The prime rating applies when the generator is the main power source; the standby rating is for backup during grid outages, with limited running hours. Every model on this page is rated 30 kVA prime.